209--Power system lab Manual by Prof.Mrs. V. K. Thombare
Sheet Report 1
Object
Power System
Components
Objectives
To study-
1.
Single line Diagram of power system
2.
D.C .Radial Distribution System
3.
A.C. Distribution Radial System
4.
Ring main system
5.
Interconnected System
Theory
The conveyance
of electric power from a power station to consumes’ premises is known as
Electric supply system. A electrical supply system consist of three principal
components viz. the power station, the transmission lines, and the distribution
system.
Electrical power is produced at the
power stations which are located at favorable places, generally quite away from
the consumers. It is transmitted over large distance to load centers with the
help of conductors known as transmission lines. Finally, it is distributed to a
large number of small and big consumers through a distribution network.
The electric
supply system can be classified into i) d.c. or a.c. system (ii) overhead or
underground system. Figure shows the layout of a typical a.c. power supply
scheme by a single line diagram.
(i)
Generating Station:
In the figure
G.S. represents the generating station where electric power is produced by
3-phase alternators operating in parallel. The usual generating voltage is
11kv.
(ii)
Transmission System:
The transmission
of electric power at high voltage has several advantages including the saving
of conductor material and high transmission efficiency.
(a)
Primary Transmission:
The electric
power at 132kv is transmitted by 3-phase, 3-wire overhead system to the
outskirts of the city. This forms the primary transmission.
(b)
Secondary Transmission:
The primary
transmission line terminates at the receiving station (RS) which usually lies
at the outskirts of the city. At the receiving station, the voltage is reduced
to 33kv by step down transformer.
(iii)
Distribution System:
(a)
Primary Distribution:
The secondary
transmission line terminates at the sub-station (SS) where voltage is reduced
from 33kv to11kv, 3-phase, 3-wire. The 11kv lines run along the important road
sides of the city.
(b) Secondary
Distribution:
The electric
power from primary distribution line(11kv) is delivered to distribution
substation(DS). These sub-stations are located near the consumers locality and
step down voltage to 400V, 3-phase, 4-wire for secondary distribution.
.
Conclusion
Questions
1.
What
is electrical power system? Draw a single line diagram of a typical a.c power
supply scheme
2.
What
are the advantages and disadvantage of d.c transmission over a.c transmission?
3.
Explain
the following systems of distribution:
(i)
Radial
Systems
(ii)
Ring
main systems
(iii)
Interconnected
systems
Sheet Report 2
Object
Insulator
Objectives
To understand Construction and ratings of Insulators.
Theory
- Pin Type Insulator:
As the name suggest, the pin type insulator is secured to the
cross-arm on the pole. There is groove on the upper end of the insulator for
housing the conductor. The conductor passes through this groove and is bound by
the annealed wire of the same material as the conductor.
Pin type insulator are used for transmission and distribution
of electric power at voltage up to 33kv.
- Suspension Type
Insulator:
The Suspension type of insulator consist of a number of
porcelain discs connected in series by metal links in the form of strings. The
conductor is suspended at the bottom end of the string while the other end of
the string is secured to the cross arm of the tower. Each unit or disc is
designed for low voltage, say 11kv. The number of the disc in series would
obviously depend upon the working voltage.
3.
Stain Insulator:
When there is dead
end of the line or there is corner or sharp curve, the line is subjected to
greater television. In order to relieve the line of excessive tension, strain
insulators are used. The discs of strain insulator are used in the vertical
plane. When the tension in lines is exceedingly high, as at long river spans,
two or more strings are used in parallel.
4.
Shackle Insulator:
In early days, the shackle insulator were used as strain
insulators. But now a days, they are frequently used for low voltage
distribution lines. Such insulator can be used either in a horizontal position
or in a vertical position. They can be directly fixed to the pole with a bolt
or to the cross arm.
Conclusion
Questions
1.
Discuss
the advantages & Disadvantages of
i)
Pin
Type Insulator
ii)
Suspension
Type Insulator
2.
Why
are insulators used with overhead lines? Discuss the desirable properties of
Insulators.
3.
Explain
the terms:
i)
Stain Insulator
ii)
Shackle Insulator
Sheet Report 3
Object
Underground
cables
Objectives
To understand
the Construction and Classification of Cables,
Theory
Underground
cables:
Underground
Cables:
An underground cable essentially consists of one or more conductors covered with suitable insula- tion and surrounded by a protecting
cover.
Constuction of Cable:
(i) Cores or Conductors.
A cable may have one or more than one core (conductor) depending upon the type of service for which it is intended. For instance, the 3-conductor cable
shown in Fig. 11.1 is used for 3-phase service.
The conductors are made of tinned copper or alu- minium and are usually
stranded in order to provide
flexibility to the cable.
(ii) Insulatian. Each
core or conductor is provided with a suitable thickness
of insulation, the thickness of layer depending upon the voltage
to be withstood by the cable. The commonly
used materials for insulation are impregnated paper, varnished
cambric or rubber mineral compound.
(iii) Metallic sheath. In order to pro- tect the cable from moisture, gases or other damaging liquids (acids or alkalies) in the soil and
atmosphere, a metallic sheath of lead or aluminium is provided over the insulation
as shown in Figure.
(iv)
Bedding. Over the metallic sheath is applied
a layer of bedding which consists of a fibrous
material like jute or hessian tape. The purpose of bedding is to protect the metallic sheath against corrosion and from
mechanical injury due to armouring.
(v) Armouring.
Over the bedding, armouring is provided which consists of one or two layers of galvanised steel wire or steel tape. Its purpose is to protect the cable from mechanical injury while laying it and during
the course of handling. Armouring may not be done in the case of
some cables.
(vi) Serving. In
order to protect
armouring from atmospheric conditions, a layer of fibrous material (like jute) similar to
bedding is provided over the armouring. This is known as Serving
Belted Cables—Upto 11Kv
Screened Cables—Upto 22Kv to 66Kv
Pressure Cables—Beyond 66Kv.
Conclusion
Questions
1. Compare the merits and demerits of
underground systems versus overhead system.
2. Explain the terms:
i)
Belted Cables
ii)
Screened Cables
iii)
Pressure Cables
Experiment no. 1
Object
GMD & GMR, Inductance and Capacitance of 3 Phase Transposed Line
Objectives
To Find Out GMD & GMR, Inductance and Capacitance of 3 Phases
Transposed Line
Theory
Consider the three-phase line shown in
Figure, Each of the conductors has a radius of r and their centers form an
equilateral triangle with a distance D between them. Assuming that the
currents are balanced, we have
Ia+Ib+Ic=0
Consider a point P external to the conductors. The
distance of the point from the phases a, b and c are denoted by Dpa, Dpband Dpcrespectively.
Fig: Three-phase symmetrically spaced conductors and an
external point P
Let us assume that the flux linked by the
conductor of phase-a due to a current Ia includes
the internal flux linkages but excludes the flux linkages beyond the point P . Then from (1.18)we
get
The flux linkage with the conductor of
phase-a due to the current Ib ,
excluding all flux beyond the point P , is given by as
Similarly the flux due to the current Ic is
Therefore the total flux in the phase-a
conductor is
The above expression can be expanded as
we get,
Substituting the above expression in eqn.
Now if we move the point P far away, then we can
approximate Dpa Dpb Dpc.. Therefore their logarithmic
ratios will vanish and we can write as
Hence the inductance of phase-a is given as
CA=
F/m
.
Apparatus
MATLAB software, Power
system analysis By Hadi sadad Tool Box
Procedure
1.Open MATLAB Window
2.Open matlab program from Hadi sadat ref example no.4.4
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
A 735KV three phase transposed line is composed of 4
ACSR 954,000 cmil 45/7 rail conductor per phase with horizontal conductor
configuration as shown in fig. Bundle spacing is 46 cm. Use ACSR in MATLAB to
obtain the conductor size and the electrical characteristics for rail
conductor. Find out the inductance and capacitance per phase km of the line.
[Ref: Example
4.4, Power System Analysis, Hadi Sadat]
Manually calculation
MATLAB
Input:
[GMD, GMRL, GMRC] = gmd;
L=0.2*log(GMD/GMRL)
C = 0.0556/log(GMD/GMRC)
Output:
Number of
three-phase circuits
Enter
------------------------------ -----
Single-circuit line 1
Double-circuit vertical configuration 2
Double-circuit horizontal
configuration 3
To quit 0
b
O For spacing unit
use
/ \ m within quotes
or
/
\ ft
within quotes.
/
\
D12
D23
/ \ a b c
/
\
O----D12----O----D23----O
a/ \c
O------D13------O OR
----------D13----------
Enter spacing
unit within quotes 'm' or 'ft'-> 'ft'
Enter row vector
[D12, D23, D13] = [45.5 45.5 89]
Cond. size,
bundle spacing unit: Enter 'cm' or 'in'-> 'cm'
Conductor
diameter in cm = 2.959
Geometric Mean
Radius in cm = 1.173
No. of bundled
cond. (enter 1 for single cond.) = 4
Bundle spacing
in cm = 46
Result
GMD = 56.90332 ft
GMRL =
0.65767 ft
GMRC =
0.69696 ft
L = 0.8921
C = 0.0126
Conclusion
Questions
1.
What
is Transposition
2.
Expression
for the inductance per phase for a 3-phase symmetrical transposed overhead
transmission line
3.
Expression
for the inductance per phase for a 3-phase unsymmetrical transposed overhead
transmission line.
4.
Derive
an expression for flux linkage
i)
Due to
single current carrying conductor
ii)
In
parallel current carrying conductor
Experiment no. 2
Object
GMD & GMR, inductance and capacitance of double circuit 3 phase
Transposed line with vertical conductor configuration.
Objectives
To find out GMD & GMR,
inductance and capacitance of double circuit 3 phase Transposed line with
vertical conductor configuration
Theory
Consider the three-phase transposed line
shown in Figure In this the charges on conductors of phases a, b and c are qa, qband qc respectively. Since the system is
assumed to be balanced we have
Fig:Charge on a three-phase transposed line
Using superposition, the voltage Vab for the first, second and third
sections of the transposition are given respectively as
Then the average value of the voltage is
This implies
The GMD of the conductors is given in
(1.42). We can therefore write
Similarly the voltage Vac is given as
For a set of balanced three-phase voltages
Therefore we can write
For bundles conductor
Apparatus
MATLAB software, Power
system analysis By Haadi sadad Tool Box
Procedure
1.Open MATLAB Window
2.Open matlab program from Haadi sadat ref example no.4.4
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example:
A 345 kv double circuit 3 phase
Transposed line is of two ACSR ,1,431,000-cmil,45/7 bobolink conductors per
phase with vertical conductor configuration as shown in fig. The conductor have
a diameter of 1.427 in and a GMR of 0.564 in. The bundle spacing is 18 in. find
out the inductance and capacitance per
phase of the line.
[Ref: Example
4.5, Power System Analysis, Haadi Sadat]
Manually calculation
MATLAB Code
[GMD, GMRL, GMRC] = gmd;
L=0.2*log(GMD/GMRL)
C = 0.0556/log(GMD/GMRC)
MATLAB Output
Number of three-phase circuits Enter
------------------------------
-----
Single-circuit
line 1
Double-circuit
vertical configuration 2
Double-circuit
horizontal configuration 3
To quit 0
a c`(a`)
Circuit Arrangements O-----S11-----O For spacing unit use
-------------------- | m within quotes or
(1)
abc-c`b`a` H12 ft within quotes.
(2)
abc-a`b`c` b | b`(b`)
O--------S22--------O
|
H23
c| a`(c`)
O----S33----O
Enter (1 or 2)
-> 2
Enter spacing
unit within quotes 'm' or 'ft'-> 'm'
Enter row vector
[S11, S22, S33] = [11 16.5 12.5]
Enter row vector
[H12, H23] = [7 6.5]
Cond. size,
bundle spacing unit: Enter 'cm' or 'in'-> 'in'
Conductor
diameter in inch = 1.427
Geometric Mean
Radius in inch = 0.564
No. of bundled
cond. (enter 1 for single cond.) = 2
Bundle spacing
in inch = 18
Result
GMD = 12.03227 m
GMRL = 1.03122 m
GMRC = 1.09366 m
L = 0.4914
C =0.0232
Conclusion
Questions
1.
Different
types of conductor
2.
What
is GMD & GMR
3.
Define
i)
Skin
Effect
ii)
Proximity
Effect
4.
Expression
for the inductance per phase for a 3-phase symmetrical transposed overhead
transmission line.
5.
Expression
for the inductance per phase for a 3-phase unsymmetrical transposed overhead
transmission line
Experiment no. 3
Object
Sending end voltage ,voltage Regulation and power of Short Line
Objectives
Student should able to calculate ABCD Parameters, Sending end
current,Voltage,Active & Reactive
Power & voltage Regulation using Nominal π Method
Theory
Short transmission lines. When the length of an
overhead transmission line is upto about 50 km and the line voltage is
comparatively low (< 20 kV), it is usually considered as a short transmission
line. Due to smaller length and lower voltage, the capacitance effects are
small and hence can be neglected. Therefore, while studying the performance of
a short transmisison line, only resistance and inductance of the line are taken
into account.
Consider a per phase short transmission line model shown in
fig. where,
VS & IS
sending end voltage and current
VR & IR
receving end voltage and current
If a three-Phase load with apparent
power SR(3Φ) is connected at the end of the transmission line, the
receving end current is obtained by,
The phase voltage at the sending end is
Since shunt capacitance is neglected in short transmission
line,
The
transmission line is represented by a two port network (ABCD parameter) given
below
By
comparing equation 1,2 and 3
Apparatus
MATLAB software, Power system analysis By Haadi sadad Tool
Box
Procedure
1.Open MATLA Window
2.Open matlab program from Haadi sadat ref example no.5.1
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
[Ref: Example 5.2, Power System Analysis,
Haadi Sadat]
Manually calculation
MATLAB Code
VRLL=220; VR = VRLL/sqrt(3);
Z = (0.15+j*2*pi*60*1.3263e-3)*40;
disp('(a)')
SR=304.8+j*228.6;
IR = conj(SR)/(3*conj(VR)); IS = IR;
VS = VR + Z*IR;
VSLL = sqrt(3)*abs(VS)
SS = 3*VS*conj(IS)
REG = (VSLL - VRLL)/VRLL*100
Eff = real(SR)/real(SS)*100
disp('(b)')
SR=304.8-j*228.6;
IR = conj(SR)/(3*conj(VR)); IS = IR;
VS = VR + Z*IR;
VSLL = sqrt(3)*abs(VS)
SS = 3*VS*conj(IS)
REG = (VSLL - VRLL)/VRLL*100
Eff = real(SR)/real(SS)*100
Output
a)
VSLL =250.0186
SS =3.2280e+002
+2.8858e+002i
REG =13.6448
Eff = 94.4252
(b)
VSLL =210.2884
SS =3.2280e+002
-1.6862e+002i
REG = -4.4144
Eff = 94.4252
Conclusion
Questions
1. Analysis of short transmission Line and also evaluate
constant for it.
Experiment no. 4
Object
Receiving end voltage, power, voltage regulation of medium line
Objectives
Student should able to calculate ABCD Parameters, Sending end
current,Voltage,Active & Reactive
Power & voltage Regulation using Nominal T Method
Theory
Medium transmission lines are
modeled with lumped shunt admittance. There are two different representations -
nominal-p and nominal-T depending on the
nature of the network.
Nominal-p
Representation:
In this representation the lumped
series impedance is placed in the middle while the shunt admittance is divided
into two equal parts and placed at the two ends. The nominal-p
representation is shown in Figure. This representation is used for load flow
studies, as we shall see later. Also a long transmission line can be modeled as
an equivalent p-network for load flow studies.
Figure: Nominal-p representation
Let us define
three currents I1, I2 and I3
as indicated in Fig. 2.3. Applying KCL at nodes M and N we get
Again
Substituting (2) in (1) we get
Therefore from
(2) and (2) we get the following ABCD parameters of the nominal-p representation
Apparatus
MATLAB software, Power
system analysis By Haadi sadad Tool Box
Procedure
1.Open MATLA Window
2.Open matlab program from Haadi sadat ref example no.5.2
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
A 345 kv three phase transmission
line is 130 km long. The resistance per phase is 0.036Ω per km and inductance per
phase is 0.8mH per km. The shunt capacitance is 0.0112μF per Km. The receiving
end load is 270 MVA with 0.8 P.F. lagging at 325 kv. Use the medium line model to find out the voltage, voltage
regulation and power at sending end.
[Ref: Example
5.2, Power System Analysis, Haadi Sadat]
Manually calculation
MATLAB Code
r = .036; g = 0; f = 60;
L = 0.8; %
milli-Henry
C = 0.0112; %
micro-Farad
Length = 130; VR3ph =
325;
VR = VR3ph/sqrt(3) + j*0;
% kV (receiving end phase voltage)
[Z, Y, ABCD] = rlc2abcd(r, L, C, g, f, Length);
AR = acos(0.8);
SR = 270*(cos(AR) + j*sin(AR)); %
MVA (receiving end power)
IR = conj(SR)/(3*conj(VR)); %
kA (receiving end current)
VsIs = ABCD* [VR; IR]; % column vector [Vs; Is]
Vs = VsIs(1);
Vs3ph = sqrt(3)*abs(Vs); % kV(sending end L-L voltage)
Is = VsIs(2); Ism = 1000*abs(Is); %
A (sending end current)
pfs= cos(angle(Vs)- angle(Is)); %
(sending end power factor)
Ss = 3*Vs*conj(Is); % MVA (sending end power)
REG = (Vs3ph/abs(ABCD(1,1)) - VR3ph)/VR3ph *100;
fprintf(' Is = %g A', Ism), fprintf(' pf = %g\n', pfs)
fprintf(' Vs = %g L-L kV\n', Vs3ph)
fprintf(' Ps = %g MW', real(Ss)),
fprintf(' Qs = %g
Mvar\n', imag(Ss))
fprintf(' Percent voltage Reg. = %g\n', REG)
Output
Enter 1 for Medium line or 2 for long line --> 1
Nominal pi model
----------------
Z = 4.68 + j 39.2071
ohms
Y = 0 + j 0.000548899
Siemens
0.98924 + j
0.0012844 4.68 + j 39.207
ABCD =
-3.5251e-007 +
j 0.00054595 0.98924 + j 0.0012844
Is = 421.132 A pf = 0.869657
Vs = 345.002 L-L kV
Ps = 218.851 MW Qs = 124.23 Mvar
Percent voltage Reg. =
7.30913
Conclusion
Questions
1. Evaluate the generalized circuit constants for Medium π
Network.
2. Voltage Regulator
3.Method of Voltage control
Experiment no. 5
Object
Receiving end voltage, power, voltage regulation of medium line
Objectives
Use the medium line model to find out the voltage, current, voltage regulation
and power at receiving end..
Theory
In this
representation the shunt admittance is placed in the middle and the series
impedance is divided into two equal parts and these parts are placed on either
side of the shunt admittance. The nominal-T representation is shown in Figure
Let us denote the midpoint voltage as VM. Then the
application of KCL at the midpoint results in
Figure:
Nominal-T representation
Rearranging the above equation can be written as
Now the receiving end current is given by
Substituting the value of VM from (1) in
(2) and rearranging we get
Furthermore the sending end current is
Then substituting the value of VM from (1)
in (3) and solving
Then the ABCD parameters of the T-network are
Apparatus
MATLAB software, Power
system analysis By Haadi sadad Tool Box
Procedure
1.Open MATLA Window
2.Open matlab program from Haadi sadat ref example no.5.3
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
A 345 kv three phase transmission
line is 130 km long.The series impedance z =
.036 + j* 0.3Ω per phase per km, the shunt admittance is y=j4.22*10-6.
The sending end voltage is 345 kv and sending end current is 400 A at 0.95 p.f.
lag. Use the medium line model to find out the voltage,
current, voltage regulation and power at
receiving end.
[Ref: Example
5.3, Power System Analysis, Haadi Sadat]
Manually calculation
MATLAB Code
z = .036 + j* 0.3; y =
j*4.22/1000000; Length = 130;
Vs3ph = 345; Ism =
0.4; %KA;
As = -acos(0.95);
Vs = Vs3ph/sqrt(3) + j*0; % kV (sending end phase voltage)
Is = Ism*(cos(As) + j*sin(As));
[Z,Y, ABCD] = zy2abcd(z, y, Length);
VrIr = inv(ABCD)* [Vs; Is]; %
column vector [Vr; Ir]
Vr = VrIr(1);
Vr3ph = sqrt(3)*abs(Vr); % kV(receiving end L-L voltage)
Ir = VrIr(2); Irm = 1000*abs(Ir);% A (receiving end current)
pfr= cos(angle(Vr)- angle(Ir)); %
(receiving end power factor)
Sr = 3*Vr*conj(Ir); % MVA (receiving end power)
REG = (Vs3ph/abs(ABCD(1,1)) - Vr3ph)/Vr3ph *100;
fprintf(' Ir = %g A', Irm), fprintf(' pf = %g\n', pfr)
fprintf(' Vr = %g L-L kV\n', Vr3ph)
fprintf(' Pr = %g MW', real(Sr))
fprintf(' Qr = %g
Mvar\n', imag(Sr))
fprintf(' Percent voltage Reg. = %g\n', REG)
Output
Output:
Enter 1 for Medium line or 2 for long line --> 1
Nominal pi model
----------------
Z = 4.68 + j 39 ohms
Y = 0 + j 0.0005486
Siemens
0.9893 + j 0.0012837 4.68
+ j 39
ABCD =
-3.5213e-007 +
j 0.00054567 0.9893 + j 0.0012837
Result
Ir = 441.832 A pf = 0.887501
Vr = 330.68 L-L kV
Pr = 224.592 MW Qr = 116.612 Mvar
Percent voltage Reg. =
5.45863
Conclusion
Questions
1. Evaluate the generalized circuit constants for Medium T
Network.
2. Analysis of short transmission Line and also evaluate
constant for it.
Experiment no. 6
Object
Surge Impedance Loading
Objectives
Use the medium line model to find out the voltage, current, voltage
regulation and power at sending end..
Theory
Surge impedance load is the load (of unity power factor) that can be
delivered by the line of negligible resistance.
When the line is
loaded by being terminated with an impedance equal to its characteristic
impedance, the receiving end current is
For a lossless
line ZC is purely resistive. The load corresponding to the surge
impedance at rated voltage is kown as the surge impedance loading (SIL) given
by
Where, VR is
the receiving end voltage in kV and ZC is the surge impedance in ohms, and
SIL is the surge impedance loading or natural loading of the line
The above
expression gives a limit of the maximum power that can be delivered by a line
and is useful in designing the transmission line. This can be used for the
comparison of loads that can be carried on the transmission lines at different
voltages
From the above expression power transmitted through a long
transmission lines can be either increased by increasing the value of the
receiving end line voltage (VR )
or by reducing the surge impedance (ZC). Voltage transmission
capability is increased day by day; this is the most commonly adopted method
for increasing the power limit of the heavily loaded transmission line. But
there is a limit beyond which is neither economical nor practical to increase
the receiving end line voltage
By applying some methods such as introducing series
capacitors (capacitors in series with the transmission line) or shunt
capacitors (capacitors in parallel with transmission lines) can be used to
reduce the value of surge impedance (ZC).
At natural
as impedance is purely resistive,
Example
[Ref: Example
5.5, Power System Analysis, Haadi Sadat]
Manually calculation
MATLAB Code
L=0.97; C=0.0115; lngth=300;
SR=800+j*600; VRLL = 500;
w=2*pi*60;
beta=w*sqrt(L*C*1e-9)
Zc = sqrt(L/C*1e3)
vel=1/sqrt(L*C*1e-9)
lambda=vel/60
betal=beta*lngth;
VR=VRLL/sqrt(3);
IR=conj(SR)/(3*conj(VR));
VS=cos(betal)*VR+j*Zc*sin(betal)*IR;
VSLL=sqrt(3)*abs(VS)
IS =
j/Zc*sin(betal)*VR+cos(betal)*IR;
ISM=abs(IS)*1000
SS=3*VS*conj(IS)
A=abs(cos(betal));
REG=(VSLL/A - VRLL)/VRLL*100
Output
beta = 0.0013
Zc = 290.4270
vel = 2.9941e+005
lambda = 4.9902e+003
VSLL = 617.5458
ISM = 902.3314
SS = 8.0000e+002 +5.3992e+002i
REG = 32.8766
Conclusion
Questions
Explain SIL.
Experiment no. 7
Object
Complex power flow
Objectives
Student should able to calculate
complex power flow for each source and losses using MATLAB
Theory
Apparatus
MATLAB software, Power system analysis By Haadi sadad Tool
Box
Procedure
1.Open MATLA Window
2.Open matlab program from Haadi sadat ref example no.1.1
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
1)
Two voltage sources V1=120∟-5 V and V2 =100∟0 V are connected
by short line of impedance Z=1+j7Ω as shown in fig. above. Determine the real
and reactive power supplied or received by each source and the power loss in
the line.
2)
Write a MATLAB program for a system of above Example such
that the phase angle of source 1 is changed from its initial value by ±300
in steps of 50 . Voltage magnitude of the two sources and
voltage phase angle of sources 2 is to be kept constant. Compute the complex
power for each source and the line losses. Tabulate the real power and plot p1
, p2 and pL versus voltage phase angle δ.
[Ref: Example
2.5 and 2.6, Power System Analysis,
Haadi Sadat]
Manually calculation
MATLAB Code
1)
R = 1; X = 7; Z = R +j*X;
V1 = 120*(cos(-5*pi/180) +
j*sin(-5*pi/180));
V2 = 100+j*0;
I12 = (V1 - V2)/Z, I21 = -I12;
S12 = V1*conj(I12), S21 =
V2*conj(I21)
SL = S12 + S21
PL = R*abs(I12)^2, QL = X*abs(I12)^2
2)
E1=input('Source # 1 Voltage Mag. =
');
a1=input('Source # 1 Phase Angle = ');
E2=input('Source # 2 Voltage Mag. =
');
a2=input('Source # 2 Phase Angle = ');
R=input('Line Resistance = ');
X= input('Line Reactance = ');
Z= R + j*X; % line
impedance
a1 = (-30+a1:5:30+a1)'; % change a1 by +/- 30 deg., col. array
a1r = a1*pi/180; % convert degree to
radian
k=length(a1);
a2=ones(k,1)*a2; % create col. array of same length for
a2
a2r = a2*pi/180; % convert degree to
radian
V1=E1.*cos(a1r) + j*E1.*sin(a1r);
V2=E2.*cos(a2r) + j*E2.*sin(a2r);
I12 = (V1 - V2)./Z; I21=-I12;
S1= V1.*conj(I12); P1 = real(S1); Q1 = imag(S1);
S2= V2.*conj(I21); P2 = real(S2); Q2 = imag(S2);
SL= S1+S2; PL = real(SL); QL = imag(SL);
Result1=[a1, P1, P2, PL];
disp(' Delta 1
P-1 P-2 P-L ')
disp(Result1)
plot(a1, P1, a1, P2,
a1, PL), grid
text(-26, -550, 'P1'), text(-26,
600,'P2'), text(-26, 100, 'PL')
xlabel('Source #1 Voltage Phase
Angle'), ylabel('P, Watts')
Output
I12 = -1.0733 -
2.9452i
S12 =-9.7508e+001 +3.6331e+002i
S21 =1.0733e+002 -2.9452e+002i
SL = 9.8265 +68.7858i
PL =9.8265
QL = 68.7858
2)
Source # 1 Voltage Mag. = 120
Source # 1 Phase Angle
= -5
Source # 2 Voltage Mag. = 100
Source # 2 Phase Angle
= 0
Line Resistance = 1
Line Reactance = 7
Conclusion
Experiment no. 8
Object
Load curve
Objectives
Student should able to calculate
load factor using MATLAB
Theory
Load Curves
The curve
showing the variation of load on the power station with respect to (w.r.t)
time is known as a load curve.
The load on a power station is never constant; it varies from
time to time. These load variations during the whole day (i.e., 24
hours) are recorded half-hourly or hourly and are plotted against time on the
graph. The curve thus obtained is known as daily load curve as it shows
the variations of load w.r.t. time during the day.
Importance. The daily load curves have attained a great importance in
generation as they sup-ply the following information readily :
(i) The daily load
curve shows the variations of load on the power station during different hours
of the day.
(ii) The area under
the daily load curve gives the number of units generated in the day. Units
generated/day = Area (in kWh) under daily load curve.
(iii) The highest
point on the daily load curve represents the maximum demand on the station on
that day.
(iv) The area under
the daily load curve divided by the total number of hours gives the average load
on the station in the day.
(v) The ratio of the
area under the load curve to the total area of rectangle in which it is
con-tained gives the load factor.
(vi) The load curve
helps in selecting* the size and number of generating units.
(vii) The load curve
helps in preparing the operation schedule of the station.
Important Terms and Factors
(i)
Connected load. It is the sum of continuous ratings of all the equipments
connected to supply system.
(ii)
Maximum demand : It is the greatest demand of load
on the power station during a given period.
(iii)
Demand factor. It is the ratio of maximum demand on the power
station to its connected load i.e.
(iv)
Average load. The average of loads occurring on the power
station in a given period (day or month or year) is known as average
load or average demand.
(v) Load factor. The ratio of
average load to the maximum demand during a given period is known as load factor i.e.
(vi)
Diversity factor. The ratio of the sum of individual maximum demands to the
maximum demand on power station is known as diversity factor i.e.,
(vii)
Plant capacity factor. It is the ratio of actual energy produced to the maximum
possible energy that could have been produced during a given period
i.e.,
(viii) Plant use factor. It is ratio of
kWh generated to the product of plant capacity and the number of hours
for which the plant was in operation i.e.
Apparatus
MATLAB software, Power system analysis By Haadi sadad Tool Box
Procedure
1.Open MATLA Window
2.Open matlab program from Haadi sadat ref example no.1.1
3.Execuite the program
4.Check the output
5.Verify the output with manual calculation.
Example
The daily load on power system is
given below. Use barcyle function to obtain a plot of the daily load curve.
Using the given data compute the average load and daily load factor.
[Ref: Example
1.1, Power System Analysis, Haadi Sadat]
Manually calculation
MATLAB Code
data = [ 0 2 6
2 6 5
6 9 10
9 12 15
12 14 12
14 16 14
16 18 16
18 20 18
20 22 16
22 23 12
23 24
6];
P =data(:,3); % Column array
of load
Dt = data(:, 2) - data(:,1); %
Column array of demand interval
W = P'*Dt;
% Total energy, area under the curve
Pavg = W/sum(Dt) % Average
load
Peak = max(P) % Peak
load
LF = Pavg/Peak*100 % Percent load
factor
barcycle(data) % Plots the load
cycle
xlabel('Time, hr'), ylabel('P, MW'), grid
Output
Pavg = 11.5417
Peak =18
LF =64.1204
Load curve
Conclusion
electricalamgoi.wix.in
Comments
Post a Comment